DUC2-NH Digital Ammonia Controller for Wastewater
Get Latest PricePayment Type: | L/C,Western Union,D/P,D/A,T/T,MoneyGram |
Incoterm: | FOB,CIF,EXW,CFR,DDP |
Min. Order: | 1 Piece/Pieces |
Transportation: | Ocean,Land,Air,Express |
Payment Type: | L/C,Western Union,D/P,D/A,T/T,MoneyGram |
Incoterm: | FOB,CIF,EXW,CFR,DDP |
Min. Order: | 1 Piece/Pieces |
Transportation: | Ocean,Land,Air,Express |
Model No.: DUC2-NH
Brand: daruifuno
Resolution: 0.01mg/L
Relay Control: Two SPST relays
Communication: RS485 Modbus RTU
Display: 3.2 inch
Data Recording: 10000 historical data
Dimension: 144*144*120mm
Support Customization: Oem
Place Of Origin: China
Product Name: Ammonia nitrogen meter
Display Range: 0-1000mg/L
Daruifuno's online ammonia nitrogen controller is a digital instrument. It can be connected with the digital ammonia nitrogen sensor of the ion selection method to realize real-time monitoring of the ammonia nitrogen value of the water quality. The Ammonia Controller is widely used in water treatment plants, sewage plants, industrial production processes, etc., where ammonia nitrogen content needs to be monitored. The ammonia controller has two SPST relays for control system and clean control. It has two 4-20mA current output and a two-wire RS485 interface, support Modbus protocol. The ammonia controller can display NH4-N and pH values at the same time.
Features of NH4-N Controller
Specification of NH4-N Controller
Product Name | ammonia nitrogen analyzer |
Product Model | DUC2-NH |
Brand Name | Daruifuno |
Display Rang | 0-1000mg/L |
Resolution | 0.01mg/L |
Relay Control | 2 settable SPST relays with a maximum load of 3A/250VAC |
Analog Current Output | 2 settable 0/4~20mA active current loop outputs, max load 1000Ω |
Communication Method | RS485 interface; MODBUS RTU; support JSON text data format |
Display Screen | 128*64 LCD, adjustable backlight mode, adjustable display rate |
Configuration Information | Power off protection, parameters are retained indefinitely |
Time/Data Record | Record 10000 historical data |
Maintenance Records | Last 100 |
Operating Environment | 0~60℃,RH<95% ( no condensation) |
Storage Environment | -20~70℃, RH<55% ( no condensation, precision instruments) |
Shell Material | Enhanced ABS |
Protection Grade | IP66 |
Dimension | 144*144*120mm |
Mounting Method | Wall mounting, pipe clamping, panel (hole size 138*138 mm) |
Electrical Interface | Reserved 3 M12*1.5 Grand head, line diameter 3~6.5 mm |
Power Supply | AC: 100~240V 50/60Hz or DC: 18~36V |
Power Consumption | 7W |
Weight | 800g |
In addition to ammonia nitrogen controller, our company also has Ph Orp Analyzer, Conductivity Analyzer, Turbidity Analyzer, Cod Analyzer, Dissolved Oxygen Analyzer, chlorine analyzer and so on. Our products are suitable for various water treatment occasions, if you are interested in our products, please contact us.
Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.
Fill in more information so that we can get in touch with you faster