Laser Online Turbidity Sensor for Circulating Cooling Water
Get Latest PricePayment Type: | L/C,T/T,Paypal |
Incoterm: | FOB,EXW,CFR,CIF |
Min. Order: | 1 Piece/Pieces |
Transportation: | Express |
Payment Type: | L/C,T/T,Paypal |
Incoterm: | FOB,EXW,CFR,CIF |
Min. Order: | 1 Piece/Pieces |
Transportation: | Express |
Model No.: OLTU600
Brand: daruifuno
Certification: Ul
Support Customization: Oem
Place Of Origin: China
Product Name: online turbidity sensor
Measuring Principle: 660nm laser scattering
Resolution: 0.001NTU
Communication: RS485
Power Supply: 9~18V DC
Material: ABS
Selling Units | : | Piece/Pieces |
Package Type | : | Cardboard boxes |
Circulating water generally refers to industrial circulating cooling water. In factories, cooling water is mainly used to condense steam and cool products or equipment. The OLTU600 online laser Turbidity Analyzer developed and produced by Daruifuno is mainly a precision instrument used to detect the turbidity of industrial circulating cooling water. If the cooling effect is poor, it will affect production efficiency and reduce product yield and product quality. It may even cause production accidents. According to China's domestic standards, the regulations on the turbidity of circulating water are: for intercooled open systems, according to the requirements of the production process, the general water turbidity should be ≤20NTU; if the heat exchange equipment is plate type, finned tube type, spiral plate type, Water turbidity should be ≤10NTU. It is especially widely used for water turbidity detection of water in indirect cooling open systems. In addition, for closed cooling water systems that do not use ultrafiltration purification, or when the filtration and purification effect is not good, a Turbidity Sensor should also be used to monitor in real time whether the turbidity of the cooling water meets the usage requirements. The water quality requirements for surface water, groundwater, and seawater desalination water as supplementary water for open indirect circulating cooling water systems are that the turbidity should be less than 3NTU. The water quality requirements for recycled water as supplementary water are that the turbidity should be less than 5NTU. The measurement range of the OLTU600 online turbidity sensor is between 0.001~100NTU, and it can automatically switch the range to achieve accurate measurement of low turbidity values.
Features
The OLTU600 series low range turbidimeter adopts a compact and miniaturized design with small installation space and is conducive to integration;
660nm laser light source, high resolution and fast response speed;
A version with windows and operating buttons is available
Digital turbidity sensor supports Modbus communication protocol for easy integration
Specification
Product Name | Laser turbidimeter |
Product Model | OLTU600 |
Signal Type | Digital RS485 Modbus |
Measuring Principle | 660nm laser scattering principle |
Measuring Range | 0.01~100NTU |
Accuracy | 0.001~40NTU is ± 2% of the reading or ± 0.015NTU, take the larger one; |
40~100NTU is ± 5% of the reading | |
Resolution | 0.001NTU |
Calibration | Multi-point calibration; Contrast Offset; Factor offset |
Flow requirement | 100~700mL/min |
Operating Temperature | 0~45℃ |
Shaft Material | ABS |
Protection Grade | IP65 (indoor) |
Power Supply | 9~18VDC |
It is generally stipulated that the turbidity of an open circulating water system should be less than 20 NTU. Excessive turbidity will form dirt on the heat exchanger, causing deposition and affecting the heat exchange efficiency. At the same time, excessive turbidity will increase the mechanical energy of erosion and increase metal corrosion; Excessive turbidity will also mix with microbial metabolites to form a large amount of biological slime, which will adhere to the surfaces of pipes and heat exchangers, causing dirt deposition and underscale corrosion. Therefore, it is very necessary to use laser turbidity sensors for continuous and real-time monitoring. System problems can be discovered in time and measures can be taken to solve them.
Delfino company focuses on the research, development and production of water quality instruments. Our main products include Ph Orp Analyzer, Conductivity Analyzer, turbidity analyzer, Cod Analyzer, Dissolved Oxygen Analyzer, ammonium analyzer, chlorine analyzer, etc.
according to our experience, usually the reasons for high circulating water turbidity are as follows:
Use an online turbidity analyzer for monitoring and take solutions:
If you are interested in the online turbidity analyzer, please contact us for more specific data sheet.
Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.
Fill in more information so that we can get in touch with you faster
Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.